How to handle faults in industrial chiller systems?
How to handle faults in industrial chiller systems?
1. Power on without power. ① If the power cord has poor contact, check the power interface and whether the power cord plug is properly connected and in good contact; ② Open the electrical box cover inside the machine and check if the safety tube is intact; Is the voltage of the power supply stable enough; Check if the power wiring is in good contact.
2. Flow alarm (E01 alarm displayed on the temperature controller panel), water pipe directly connected to the outlet, and no water flow at the inlet. If the water level in the water tank is too low, check the water level gauge display window and add water to the green area; And check the water circulation pipeline for leaks.
3. When connecting the device for use, there is a flow alarm (the temperature controller panel displays E01), but there is water flow when connecting the water pipe directly to the outlet or inlet, and there is no alarm. Check the water circulation pipeline for blockage, bending or deformation.
4. High water temperature alarm (temperature controller panel displays E04). ① The dust screen is blocked and has poor heat dissipation. Regularly remove and clean the dust screen Poor ventilation at the air outlet or inlet ensures smooth ventilation. ③ If the voltage is severely low or unstable, improve the power supply line or use a voltage regulator. ④ If the temperature controller parameters are set improperly, reset the control parameters or Factory reset. ⑤ Frequent startup and shutdown of the chiller to ensure sufficient cooling time (more than five minutes). ⑥ If the heat load exceeds the standard, reduce the heat load or choose a model with a larger cooling capacity.
5. Room temperature ultra-high alarm (temperature controller panel displays E02). The operating environment temperature of the chiller is relatively high. Improve ventilation and ensure that the operating environment temperature of the chiller is below 40 degrees Celsius.
6. The condensation of condensed water is severe. If the water temperature is much lower than the ambient temperature and the humidity is high, increase the water temperature or provide insulation for the pipeline.
7. When changing water, the drainage outlet drains slowly. The water inlet is not open, open the water inlet.
Related recommendations
efficient chillers
312The Importance of Efficient Chiller Operation Efficient chiller operation is critical in the context of increasing energy costs and environmental concerns. Chillers are responsible for a signif...
View detailswater chillers
198Water Chillers: An In-Depth Analysis Introduction to Water ChillersWater chillers, also known as chilled water systems, are integral to heating, ventilating, air conditioning, and refrigeration...
View detailsindustrial chiller units
218Industrial Chiller Units: A Comprehensive Overview Introduction to Industrial Chiller Units Industrial chiller units are critical components in the HVAC industry, providing precise temperatu...
View detailssupplier chiller
159The Role of Chiller SuppliersChiller suppliers act as an intermediary between the chiller manufacturers and the end - users. They are responsible for sourcing a wide range of chillers from differe...
View details
HelloPlease log in